Description
The Server Technology® PRO2 STV-4521V Switched PDU (Primary) delivers advanced power distribution, monitoring, and control for mission-critical data centers. Designed with billing-grade PIPS® (Per Inlet Power Sensing) technology, it measures current, voltage, power, energy, and more to help optimize rack-level energy use.
With network monitoring via HTTP(S), SSH, SNMP, LDAP, RS-232, and more, this unit ensures secure, real-time visibility into your power infrastructure. Its hot-swappable network card and Star Multi-Linking allow up to four circuits to share one IP address, while outlet-level switching provides remote reboot and power management.
Built for reliability, the STV-4521V supports high retention locking outlets, branch circuit protection, and operation up to 60 °C, making it ideal for high-density racks. Color-coded options and flexible mounting enhance deployment in enterprise environments.
| Category | Details |
|---|---|
| Manufacturer | Server Technology (Legrand Group) |
| Product Line | PRO2 |
| Model / SKU | STV-4521V (Primary) |
| PDU Type | Switched |
| Input Voltage | 208 V AC |
| Input Frequency | 50/60 Hz |
| Input Plug | CS8365 3P+G, 50A |
| Input Current (Rated) | 40 A |
| Input Power Capacity | 14.4 kW |
| Outlets | 48 × IEC 60320 C13 (≤12A @ 208V, 15A peak) |
| Branch Circuit Protection | (6) × 2-pole 20A circuit breakers, UL 489 compliant |
| Per-Inlet Monitoring | Current, Voltage, Power, Apparent Power, Crest Factor, Power Factor, Energy |
| Branch Current Monitoring | Yes, with SNMP/email alerts |
| Network & Security | 10/100/1000 Mbps Ethernet, RS-232, SNMPv2c/v3, HTTP/HTTPS, SSH, Telnet, LDAP/LDAPS, TACACS+, RADIUS, FTP/SFTP |
| Environmental Monitoring | Supports 2 × temperature/humidity probes |
| Operating Temperature | 32°F to 140°F (0°C to 60°C) |
| Storage Temperature | -22°F to 176°F (-30°C to 80°C) |
| Operating Humidity | 8% – 90% RH non-condensing |
| Dimensions (HxWxD) | 69.0 in × 3.25 in × 2.75 in (1753 × 83 × 70 mm) |
| Certifications | UL 62368-1, CSA C22.2 No. 62368-1, FCC Part 15 Class A, CAN ICES-003 Class A |
| Warranty | 2-year limited parts & labor (extendable) |
Payment & Security
Your payment information is processed securely, and we do not store credit card details or access your credit card information.
Return Policy (Short Summary)
We offer a 30-day return window for most unopened, factory-sealed items.
Returns must be authorized before shipping back and must include all original packaging and accessories. Opened or used items are not returnable unless defective.
Some products—such as custom orders, special-order items, audio gear, software, and LED video walls—are non-returnable. Non-defective returns may be subject to a 20–30% restocking fee, and customers are responsible for return shipping costs.
For damaged or incorrect items, please contact us immediately.
Trusted by enterprise and education leaders who need AV done right
Why Clients Choose AVENDOR for Pro AV Projects
A clear difference in expertise, service, and speed.
You may also like